Sensor contamination fault test

Sensor contamination fault test

Inspect smoke fire detectors in an environment simulated by Arizona test dust fine particles to represent dust contamination. The airflow velocity around the sample is (0.4±0.1)m/s, and the dust concentration is (100±30)mg/m³ (or the concentration specified by the manufacturer, but not greater than 200mg/m³±30mg/m³). The simulated dust contamination environment is maintained for 1 hour. Then, stop the airflow and apply dust contamination, maintain for 1 hour, during which the condition of the sample is observed and recorded.

Applicable standards:GB4715—2024 Point-type smoke fire detectors
Test range: Smoke fire detectors